location: Current position: Home >> Scientific Research >> Paper Publications

无约束气云弱点火爆炸压力实验研究

Hits:

Indexed by:期刊论文

Date of Publication:2001-01-30

Journal:化工学报

Included Journals:PKU、CSCD

Volume:52

Issue:1

Page Number:68-71

ISSN No.:0438-1157

Key Words:可燃气云;爆炸;安全

Abstract:The strength of flammable gas cloud explosion has been experimentally researched by means of acetylene-air clouds which were ignited by electric sparks.The ignition device which provides ignition energy of about 100mJ was made according to international standard ISO 6184 and American Standard NFPA68. The explosion pressure was picked up by pressure transducer with a dynamic responding time of 0.001 s and recorded by computer. By regressing the experimental data,the relationship of gas cloud explosion pressure to the initial radius of gas cloud and the distance to the center of gas cloud can be obtained. That is

p=Ar20/r
where A is a constant depending on flammable gas cloud.The damage of unrestricted gas cloud to building structure is discussed based on the strength of houses.

Pre One:爆破片技术在液下喷射灭火系统中应用

Next One:Research on explosion pressure field of semi-spherical unrestricted flammable gas clouds