location: Current position: Home >> Scientific Research >> Paper Publications

Influence of the Commutation Current Frequency on the Vacuum DC Interruption

Hits:

Indexed by:会议论文

Date of Publication:2018-01-01

Included Journals:CPCI-S

Volume:1

Page Number:231-234

Key Words:vacuum breaker; DC interruption; commutation frequency; post arc current; chopping current

Abstract:Interrupting frequency has a great influence on the breaking capacity of the breakers. In this paper, using the forced current zero method, vacuum DC interruptions were carried out in the synthetic test circuit under small current. The equipment for measuring the current was established, with which the post arc current and the chopping current were obtained. According to the results, the influence of high frequency current on DC interruption was investigated. The results indicated that the post arc current and the chopping current increased with commutation frequency. The commutation frequency and charging voltage influence the post arc current together. The chopping current reached 130A at 4.0kHz. High commutation frequency is disadvantageous for the DC interruption.

Pre One:温度及漏磁对电流互感器性能的影响

Next One:Research on Internal and External Factors Affecting Current Commutation in Vacuum