论文成果 当前位置: 中文主页 >> 科学研究 >> 论文成果
Research on key influence factors of current-transfer process based on paralleled breaking

点击次数:
论文类型:会议论文
发表时间:2013-10-20
收录刊物:EI、Scopus
摘要:Current-transfer phase-control breaking is one method of paralleled breaking. This method can make up for shortcoming of sole chamber with high rated current and high rated short-current breaking current at the same time. In addition to breaker stationary open time and computing speed of controller, the key influence factor is that controller needs accurately to compute the current-transfer time and current zero appearing moment. It will influence the best triggering moment determination of breaker driving actuator. This paper constructs its mathematical model of current transfer process. By the theory modeling with Matlab, this paper analyzes the influencing factors to current-transfer time and current zero appearing moment. From simulation procedure and result, dc component of short-circuit current and short-circuit current phase angle of contact separating moment of first open chamber, impedance parameter of paralleled circuit and arc voltage of first open chamber after contact separating both influence the current process and current zero. After breaker structure and chamber parameters are fixed, most important matter is that short-circuit current phase angle of contact separating moment of first open chamber needs to be determined accurately. ? 2013 IEEE.

 