Abstract:In order to evaluate the energy-saving effect of seawater source heat
pump units over conventional water cooled chillers precisely, various
factors that affect the energy consumption of chillers are analyzed.
Then a mathematical model of optimal chiller loading was set up on the
basis of dynamic programming theory. Through a case study of an office
building, the steps of optimal selection of heat pumps or chillers with
different capacities are brought out based on the principle that the
total energy consumption throughout the cooling season is minimized. And
the energy-saving of the seawater source heat pump units in the case
project is calculated to be 16.3%. The energy-saving evaluation method
of seawater source heat pump units provided in the paper can minimize
the calculation error as it is based on the optimal selection of
different heat pumps or chillers.