Current position: Home >> Scientific Research >> Paper Publications

Characteristics of Triggered Vacuum Switch with Single Axial Magnetic Electrode for High Frequency Current Interruption

Release Time:2019-03-11  Hits:

Indexed by: Conference Paper

Date of Publication: 2012-09-02

Included Journals: Scopus、CPCI-S、EI

Page Number: 232-235

Abstract: For the purpose of repetitive pulsed power applications, specially designed TVSs were tested under different high frequency currents in this contribution. Two TVSs named TVS-1 and TVS-2 respectively were designed to investigate the high frequency current breaking characteristics with or without an axial magnetic field (AMF) aid. The TVS with AMF at the cup-like anode can generate a magnetic field parallel to the arc column by flowing current itself. Triggered Vacuum Switches show promise for use in high-power, high-current and high-frequency conversion and switching circuits. The V/I characteristic results show that the arc voltage increases with increasing the arc current. The maximum breaking current has a sharp decreasing trend with increasing the current frequency from zero to 1 kHz, while the curves tend to be flat after 1 kHz. The AMF in the anode gives a great aid to decrease the arc voltage and increase the high frequency breaking capability of the TVS.

Prev One:Static electric field distribution of hybrid circuit breaker Based on Ansoft

Next One:采用虚拟局域网的数字化变电站数据通信仿真研究