Abstract:The characteristics of R236fa and its feasibility as refrigerant of
ejector refrigeration system are studied.Through the thermodynamic
analyses on the ejector refrigeration system,the operation efficiencies
with R141b,R123,R134a and R236fa as working fluid respectively are
compared,and the advantages and characteristics of R236fa as refrigerant
in ejector refrigeration system are drawn.The operation system
performance of the ejector refrigeration system with R236fa in different
working conditions is analyzed,and the pump power consumption,the COP
and the ejector critical geometric dimensions are analyzed.When the
cooling capacity of system is 1 000 kW,the maximum pump power is 58
kW,the diameter of the mixing chamber is 152 mm,COP reaches 0.35
maximally.The research results show that the ejector refrigeration
system with R236fa has better economical benefits and outstanding
advantages in the design and manufacture of the large-scale
refrigeration system.