舒海文

个人信息Personal Information

副教授

硕士生导师

任职 : 建环专业实验室副主任

性别:男

毕业院校:大连理工大学

学位:博士

所在单位:土木工程系

办公地点:4号实验楼220B

电子邮箱:shuhaiwen@dlut.edu.cn

扫描关注

论文成果

当前位置: 中文主页 >> 科学研究 >> 论文成果

Cooling performance test and analysis of a radiant-convective air-conditioning terminal device with parallel pipes

点击次数:

论文类型:期刊论文

发表时间:2017-04-03

发表刊物:SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT

收录刊物:SCIE、EI

卷号:23

期号:3

页面范围:405-412

ISSN号:2374-4731

摘要:A new type of air-conditioning terminal device that could be used both for cooling in summer and heating in winter was studied in the research. In order to obtain the heat transfer characteristics of the device, a test rig was set up and measured, and then the cooling capacity and the percentage of radiation heat exchange of the device were calculated and analyzed. The results show that the total cooling capacity of the device can reach 631.0 W (i.e., 143.8 W/m(2)) under the supply water temperature of 8 degrees C and the water flow rate of 240 L/h. The proportion of the radiation heat exchange rate to the total heat exchange rate is around one-third. The cooling capacity comparison between the device and the radiant cooling ceiling shows that the cooling capacity of the device increases by about 57.6% per square meter surface area over the value of the radiant cooling ceilings at the same inlet cooling medium temperature. In the end, the differences between this radiant-convective air-conditioning terminal device and other common space heating/cooling terminal devices were summerized.