The transmission characteristics of indoor particles under different ventilation conditions

Hits:

Indexed by:会议论文

Date of Publication:2017-01-01

Included Journals:CPCI-S

Volume:22

Abstract:In modern society, ventilation is an important method for removing indoor particles. This study applies the parameter of attenuation index to analyze the effect of the removal of indoor particles in the two typical ventilation strategies called ceiling exhaust and slit exhaust strategy. Experiment was conducted in a chamber and riboflavin particles were used as the indoor particles source, instantaneous microbial detection (IMD) used to measure the particulate concentration. Conclusions can be found that air exchange rate is an important factor affecting the indoor particle concentration distribution. In the process of indoor free settling(air exchange rate is 0 h(-1)), the deposition rate were 0.086 h(-1), 0.122 h(-1), 0.173 h(-1) for the particles of 0.5-1.0 mu m, 1.0-3.0 mu m and 3.0-5.0 mu m. When the air exchange rate increased to 2.5 h(-1), the differences in the attenuation index is significant. There was also a significant linear relationship between air exchange rate and attenuation index. Furthermore, the effect of the slit exhaust strategy on the removal of coarse particles is more remarkable as the increasing air exchange rate.