A New Control Logic for a Wind-Area on the Balancing Authority Area Control Error Limit Standard for Load Frequency Control

Hits:

Indexed by:期刊论文

Date of Publication:2018-01-01

Journal:ENERGIES

Included Journals:SCIE、EI

Volume:11

Issue:1

ISSN No.:1996-1073

Key Words:wind power utilization; load frequency control (LFC); balancing authority area control error (ACE) limit standard (BAAL); control logic; real power balancing; operation security

Abstract:Nowadays, the Balancing Authority Area Control Error (ACE) Limit (BAAL) Standard has been adopted to replace the Control Performance Standard 2 (CPS2) in the North American power grid. According to the new standard's mechanism, a new control logic, named Triggered Monitoring and Graded Regulation (TM-GR) is proposed. Its purpose is to improve wind power utilization, with good BAAL Standard compliance for load frequency control (LFC). With the TM logic, according to the real-time regulating ability of areas and forecasting results of wind power output, the triggering moments to give orders are found and a defined monitoring interval is set to track the succeeding fluctuation of Area Control Error (ACE). With the GR logic, based on whether or not over-limit frequency and over-limit ACE occur simultaneously, unit output is regulated in different grades. In cooperation with the existing control logic of Control Performance Standard 1 (CPS1), the proposed logic has a higher priority. From the test results, with the proposed control logic, the utilization of wind power output increases and, meanwhile, the area's control performance meets the Standard BAL-001-2 requirements. The standard deviation of the frequency deviation is less than the target value, and the duration of over-limit ACE and over-limit frequency can both be restricted to be less than 30 min.

Pre One:一种电池储能AGC控制性能评价标准

Next One:《电力系统的能量平衡》课程的创建研究