location: Current position: Home >> Scientific Research >> Paper Publications

A simplified indoor wet-bulb globe temperature formula to determine acceptable hot environmental parameters in naturally ventilated buildings

Hits:

Indexed by:期刊论文

Date of Publication:2019-08-01

Journal:ENERGY AND BUILDINGS

Included Journals:SCIE、EI

Volume:196

Page Number:169-177

ISSN No.:0378-7788

Key Words:Naturally ventilated building; Hot environment; Indoor wet-bulb globe temperature; Natural wet-bulb temperature; Globe temperature

Abstract:Indoor wet-bulb globe temperature (WBGT) has been recommended by many thermal environmental standards for evaluating the hot environment in naturally ventilated buildings. Indoor WBGT is equal to the weighted average of natural web bulb temperature and globe temperature, and thus it is not a function of indoor hot environmental parameters. It may be not possible to use indoor WBGT to determine acceptable hot environmental parameters during the design stage of naturally ventilated buildings. This study developed a simplified indoor WBGT formula based on the linearization of calculation equations of natural web bulb temperature and globe temperature, and then indoor hot environmental parameters, natural wet-bulb temperature, globe temperature and WBGT were measured in a typical naturally ventilated building to validate the proposed formula. The results show that indoor air temperature, mean radiant temperature, relative humidity and air velocity levels were 24 degrees C-40 degrees C, 30 degrees C-50 degrees C, 21%-75% and 0.1 m/s-3.0 mks. The relative errors between the measured and calculated indoor natural wet-bulb temperature, globe temperature and WBGT were all less than 5%. Hence, the proposed indoor WBGT formula was validated to be rational, which can be conveniently used to determine the acceptable hot environmental parameters during the design stage of naturally ventilated buildings. (C) 2019 Elsevier B.V. All rights reserved.

Pre One:Indoor air distribution in a room with underfloor air distribution and chilled ceiling

Next One:辐射空调房间室内空气分布特性实验研究