Hits:
Indexed by:期刊论文
Date of Publication:2014-07-24
Journal:HEAT TRANSFER ENGINEERING
Included Journals:SCIE、EI、Scopus
Volume:35
Issue:11-12,SI
Page Number:1130-1136
ISSN No.:0145-7632
Abstract:In this paper, an absorption heat transformer (AHT) with falling film of aqueous LiBr solution inside vertical spiral tubes is installed and tested. The variations of coefficient of performance (COP), thermal efficiency (E-th ), and the heat transfer coefficient of the absorber at different falling film flow rates, hot water flow rates, and operating temperatures are investigated experimentally. The results demonstrated that the coefficient of performance and thermal efficiency of the system decrease with the increase in the flow rate of LiBr solution, and the influence of flow rate of hot water on COP and E-th is insignificant. The available COP in the experiments is higher than 0.4. The heat and mass transfer coefficients of the absorber increase with the increase of the flow rate of LiBr solution, up to 400W/m(2)/K and 0.013kg/m(2)/s (temperature of waste heat is 90 degrees C). The heat transfer coefficient of the absorber increases with the increase of the temperature of waste heat, and decreases with the increase of the cooling water temperature. Meanwhile, the computer code ABSIM (Absorption Simulation) is used to simulate the AHT systems, and the simulated results are compared with the experimental data.