location: Current position: Home >> Scientific Research >> Paper Publications

Influence of the pulsed AMF arc control on the vacuum arc and post arc characteristic in vacuum interrupters

Hits:

Indexed by:Journal Papers

Date of Publication:2018-01-01

Journal:VACUUM

Included Journals:SCIE、EI、Scopus

Volume:147

Page Number:65-71

ISSN No.:0042-207X

Key Words:Vacuum arc; AMF arc control; Post arc current; Vacuum interrupter

Abstract:The paper investigates the influence of the pulsed AMF arc control on the vacuum arc and the post arc characteristic to reveal the mechanism of AMF arc control in different control time and find the proper AMF arc control. The pulsed AMF control system is designed and the pulse width is adjusted from 1.5 ms to 10 ms by changing the capacitors. The test circuit is set up in the synthetic test circuit and the test vacuum interrupter (VI) is transparent in order to observe the development of the vacuum arc by the high speed CMOS camera. The rated voltage and current of the test VI is 10 kV and 25 kA respectively. The post arc current of the test VI is measured in order to analyze the post arc characteristic, such as the post arc charge, post arc conductance and dynamic dielectric strength. The development of vacuum arc and the post arc characteristic influenced by the pulse width, magnitude and control time of the pulsed AMF is obtained, which is useful to special magnetic contacts design. (C) 2017 Elsevier Ltd. All rights reserved.

Pre One:Time-Delay Characteristics of Laser Triggered Multi-Stage Vacuum Switch

Next One:基于合闸电阻的变压器励磁涌流相控技术研究