location: Current position: Home >> Scientific Research >> Paper Publications

Fault Ride Through of Doubly Fed Induction Generator wind Turbine Based on Supercapacitors Energy Storage

Hits:

Indexed by:会议论文

Date of Publication:2011-09-23

Included Journals:EI、CPCI-S、Scopus

Volume:130-134

Page Number:2851-+

Key Words:DFIG; LVRT; supercapacitor; reactive power

Abstract:This paper proposes a low voltage ride through(LVRT) scheme of doubly fed induction generator(DFIG) based on the supercapacitors energy storage. The novel control strategy of the bi-directional converter and the grid side converter is established. Simulation model of the DFIG system is developed. Simulation results show that the presented scheme can efficiently reduce the DC-link overvoltage, supply reactive power to the power system through grid side converter, and help grid recovery under system fault, improving the LVRT capability of the system.

Pre One:永磁直驱式风力发电机的低电压穿越控制研究

Next One:用于风电功率平抑的混合储能系统及其控制系统设计