个人信息Personal Information
教授
博士生导师
硕士生导师
主要任职:Vice Dean of Graduate School
其他任职:建筑能源研究所所长
性别:男
毕业院校:哈尔滨建筑大学
学位:博士
所在单位:土木工程系
学科:供热、供燃气、通风及空调工程. 控制理论与控制工程. 建筑学
办公地点:大连市凌工路2号大连理工大学建设工程学院3号楼601室
联系方式:0411-84706260
电子邮箱:zjldlut@dlut.edu.cn
Model parameter identification of indoor temperature lag characteristic based on hysteresis relay feedback control in VAV systems
点击次数:
论文类型:期刊论文
发表时间:2019-09-01
发表刊物:JOURNAL OF BUILDING ENGINEERING
收录刊物:SCIE、EI
卷号:25
ISSN号:2352-7102
关键字:Indoor temperature lag; VAV system; Model identification; Relay feedback control; Dynamic response
摘要:The dynamic regulation process of variable air volume (VAV) systems is a typical nonlinear process, which has characteristics of mull-variable, strong coupling, and large lag. Due to the lag response characteristics of indoor temperature versus system regulation variables, it is difficult to accurately describe indoor temperature dynamic regulation characteristics based on a conventional open-loop step response test. Taking indoor temperature lag characteristic of the air conditioning system as the study object, this paper brings hysteresis relay feedback control (HRFC) into the model parameter identification of indoor temperature lag characteristic, and provides a novel method for indoor temperature lag characteristic identification of the air conditioning system. This study provides the detail implementation process of the proposed identification method. Supported by the comparative experimental study, the effectiveness and practicability of the proposed method is validated in an integrated control test rig for a VAV system. Under the condition of no prior knowledge, model parameters of indoor temperature first-order inertia plus lag link transfer function could be identified based on HRFC accurately. Results indicate that inertial time coefficients and pure lag time coefficients are convergent. The key contribution of this paper is to propose an online identification method for indoor temperature lag characteristic in dynamic regulation process of VAV system. Ifs worth noting that the proposed method may be invalid if the indoor temperature changes greatly due to some uncertainty large disturbances, however it is useful for new-built VAV system during the commissioning process.