location: Current position: Home >> Scientific Research >> Paper Publications

Energy-saving optimal control for a factual electrostatic precipitator with multiple electric-field stages based on GA

Hits:

Indexed by:期刊论文

Date of Publication:2013-09-01

Journal:JOURNAL OF PROCESS CONTROL

Included Journals:SCIE、EI、Scopus

Volume:23

Issue:8

Page Number:1041-1051

ISSN No.:0959-1524

Key Words:Electrostatic precipitator; Multiple electric-field stages; Energy-saving optimization; Genetic algorithm

Abstract:For energy-saving control of electrostatic precipitator with multiple electric-field stages, a new optimal control strategy to minimize the total power consumption by adjusting the secondary voltages subject to the dust outlet concentration requirement is suggested. The optimal problem is established on the basis of the proposed mathematical models on the secondary voltage relating to the outlet concentration, the secondary current, the primary voltage and the primary current, and is solved by the genetic algorithm. A practice application to an industrial precipitator is given as well. (C) 2013 Elsevier Ltd. All rights reserved.

Pre One:电除尘中火花击穿的动态全时域检测方法

Next One:异构总线多协议网关设计及其在电除尘监控系统中应用