Microwave disinfection in a ventilation and air-conditioning system
点击次数:
论文类型:期刊论文
发表时间:2009-05-01
发表刊物:Hunan Daxue Xuebao/Journal of Hunan University Natural Sciences
收录刊物:EI、PKU、ISTIC
卷号:36
期号:SUPPL.
页面范围:55-59
ISSN号:16742974
摘要:Because of its broad spectrum and high efficiency, the microwave disinfection was used to control the airborne microbial contaminates in VAC system. Some microwave disinfection devices were developed combined with air filter, the design and calculation method was presented, and the disinfection effects on White staphylococcus, Staphylococcus aureus, Bacillus Subtilis, Escherichi coli were measured. The results show that the major influence factors on disinfection effect are microwave power, water-content of filter material, disinfecting duration. After 15 min, the kill ratio is >90%, and the log value is >1. The microwave field is uniform and the kill effect of bacteria on each surface of filter is the same, without statistically significant difference.