Abstract:Correlation model of head, efficiency and power in connection with flow
and speed for variable speed pump in heating and air-conditioning system
was built. According to the operation characteristics of parallel pumps,
the optimal allocation situation of speed ratio of parallel pumps when
total pump power attains its lowest level was theoretically analyzed
with reference of flow of best efficiency point and speed ratio range.
Based on a series of parallel pump operating conditions in a typical
variable water flow air-conditiong system with variable differential
pressure setpoint control, pump energy saving potential was evaluated by
simulation under four control strategies, including one pump running at
full speed and another pump running at variable speed, two pumps running
at variable speed with 0. 05 speed ratio difference, 0. 1 speed ratio
difference and the same speed ratio, respectively. Theoretical analyses
and simulation results show that the speed ratio difference leads to
extremely low efficiency of one pump or several pumps. It is concluded
that the operation strategy with parallel pump running at the same speed
ratio is the optimal choice to attain maximum pump saving potential.
Note:新增回溯数据
Professor
Supervisor of Doctorate Candidates
Supervisor of Master's Candidates
Main positions:Deputy Director, Department of Civil Engineering, Dalian University of Technology
Other Post:Member of APEC EGEE&C Group
Gender:Male
Alma Mater:Harbin Institute of Technology
Degree:Doctoral Degree
School/Department:Institute of Building Energy, Dalian University of Technology
Discipline:Heat and Gas Supply, Ventilation and Air Conditioning Engineering
Business Address:417 Room, Houxing Building
Contact Information:Email:zhaotianyi@dlut.edu.cn Office:86-411-84707734
Open time:..
The Last Update Time:..